On-line monitoring system of faulty insulator based on non-touching UV pulse method | |
He,Wei1; Chen,Tao1; Liu,Xiao Ming1; Yang,Fan1; Yao,De Gui2; Xiong,Dong1 | |
2006-05-25 | |
Source Publication | Dianli Xitong Zidonghua/Automation of Electric Power Systems |
ISSN | 10001026 |
Volume | 30Issue:10Pages:69-74 |
Abstract | General methods of detecting faulty insulators include the distribution voltage method, the corona pulse current method, the infrared thermal imaging temperature measurement method and the ultrasonic method, etc. They have, however, certain disadvantages. A brand-new ultra-violet (UV) pulse method proposed, through highly sensitive solar-blind UV detector, can continuously monitor the special wave band of UV pulses of discharge on the surface of insulators online. The UV pulse method to detect the faulty insulator is used because the faulty insulator will increase the number of the insulator string's discharge pulses. An on-line monitoring system adopting the UV pulse method doesn't need to have a touch with the insulator, and hence is very suitable for detecting faulty insulators online with the check distance beyond 4 m. The proposed method has been verified by experiments with a 110 kV line insulator. |
Keyword | Faulty insulator On-line monitoring UV pulse method |
URL | View the original |
Language | 英語English |
Fulltext Access | |
Document Type | Journal article |
Collection | Personal research not belonging to the institution |
Affiliation | 1.Chongqing University,,China 2.Henan Electric Power Research Institute,,China |
Recommended Citation GB/T 7714 | He,Wei,Chen,Tao,Liu,Xiao Ming,et al. On-line monitoring system of faulty insulator based on non-touching UV pulse method[J]. Dianli Xitong Zidonghua/Automation of Electric Power Systems,2006,30(10):69-74. |
APA | He,Wei,Chen,Tao,Liu,Xiao Ming,Yang,Fan,Yao,De Gui,&Xiong,Dong.(2006).On-line monitoring system of faulty insulator based on non-touching UV pulse method.Dianli Xitong Zidonghua/Automation of Electric Power Systems,30(10),69-74. |